📐 Team training, part 3 of 4

Measuring ramps and auditing on site

This is the hands on part. By the end you will be able to work out a slope three different ways, measure a ramp properly with a level and a tape, know the numbers to check on every site, and run a whole building audit in an order that does not miss anything. The ramp planner separates geometry from named standards, and the physical accessibility guide follows the whole visitor journey.

1. What to carry

You do not need much, and everything here fits in a small bag. The first three are non negotiable.

  • A digital level, 600mm long. Also sold as a smart level or an electronic level. This is the single most useful tool you will own. Get one that reads in percent, not only degrees.
  • A tape measure, 5m or 8m. A metal one that stays rigid when extended saves a lot of frustration when measuring alone.
  • A camera. Your phone is fine. Photographs are your evidence.
  • A door pressure gauge if you can get one, for checking how much force it takes to open a door.
  • A light meter or a phone app, for checking lighting levels at signage and stairs.
  • A notebook or a tablet with your recording sheet ready to fill in.
  • Chalk or removable tape to mark measuring points so your photos line up with your notes.

Before you leave the office

Calibrate the level, every single day

A digital level drifts, and it definitely drifts if you drop it. Calibrate it at the start of every audit day following the manufacturer instructions, and calibrate it again immediately if it takes a knock. An uncalibrated level produces confident, professional looking, completely wrong numbers, and those numbers may end up in a report with your name on it.

2. Understanding slope

Slope is just how much a surface rises compared to how far it travels. Two measurements, one relationship.

  • Rise. How much it goes up, measured vertically.
  • Run, sometimes called the going. How far it travels, measured horizontally.

The same slope gets written three different ways, and you need all three.

The three ways of saying the same thing

As a ratio. 1:12 means for every 1 unit up, it travels 12 units along. Builders and standards use this most.

As a percentage. percent = (rise ÷ run) × 100. So 1 divided by 12, times 100, is 8.33%. Digital levels usually display this.

As degrees. degrees = arctan(rise ÷ run). 1:12 comes out at about 4.8 degrees. Avoid using degrees in reports, because the numbers are small and similar and it is easy to misread 4.8 as fine when it is the legal limit.

Three ramps rising the same 150mm at 1 in 20, 1 in 12 and 1 in 8All three ramps climb the same 150mm step. At 1 in 20 the ramp is 3 metres long, at 1 in 12 it is 1.8 metres long, and at 1 in 8 it is 1.2 metres long. The gentler the slope, the more length it needs. The lengths are drawn true to scale against each other, and the heights are exaggerated 2.2 times so the rise is visible at all. Drawn to one scale. Gentler always means longer.Same 150mm step, three different slopesDrawn to one scale. Gentler always means longer.1:203.0m of ramp1:121.8m of ramp1:81.2m of rampHeight shown 2.2x exaggerated so the difference is visible. Lengths are true to scale.
The same 150mm step at three slopes. A gentler ramp is not harder to build, it just needs more room.

Learn this table. It covers almost everything you will meet.

Slope conversions between ratio, percentage and degrees, with what each means in practice.
Ratio Percent Degrees What it means in practice
1:205.0%2.9°Preferred. Comfortable to self propel. Often not even counted as a ramp.
1:156.7%3.8°Good. A sensible target on a constrained site.
1:128.3%4.8°An upper slope limit in the ordinary ISO and ADA ramp provisions; other limits still apply.
1:1010.0%5.7°Too steep for a public ramp. Fails almost everywhere.
1:812.5%7.1°Dangerous. Risk of tipping backwards going up, or forwards coming down.

How to convert, without a calculator app

Ratio to percent. Divide 100 by the second number. 100 ÷ 12 = 8.33%

Percent to ratio. Divide 100 by the percent. 100 ÷ 8.33 = 12, so 1:12.

That is the only maths you need on site. If your level reads 6.2%, then 100 divided by 6.2 is about 16, so you are at roughly 1:16, which passes.

3. Running slope and cross slope

Every sloped surface has two slopes and people forget the second one constantly.

  • Running slope is along the direction you travel. This is the one everybody thinks of. Measure it pointing up and down the ramp.
  • Cross slope is side to side, across your direction of travel. Measure it by turning the level 90 degrees.

Cross slope matters because it is exhausting and it is dangerous. If a path tilts sideways, a wheelchair constantly veers downhill, so the user has to brake one wheel the whole way to travel in a straight line. On a wet tiled surface it is a fall risk for someone with a walking stick. A path can have a perfect running slope and still be unusable because of cross slope.

Keep the reference visible: ISO 21542:2021 clause 6.3.7 recommends drainage cross-fall no greater than 1:50 (2%), with an exceptional-circumstances qualification. ADA 405.3 sets ramp cross slope at 1:48 (about 2.083%) maximum. These are different boundaries. Drainage must also prevent water collecting on the route.

Running slope along the direction of travel and cross slope across itTwo panels. On the left, a ramp surface with an arrow running up it in the direction of travel, labelled running slope; assess with the selected standard. On the right, a section through a path tilted sideways, with an arrow showing a wheelchair being pulled downhill, labelled cross slope; ISO drainage recommendation 1 in 50, ADA ramp maximum 1 in 48. Measure both, in the same spot, every time.The two slopes on every surfaceMeasure both, in the same spot, every time.RUNNING SLOPEalong the way you travelcheck slope and flight lengthchair pulls downhillCROSS SLOPEside to side, across your pathISO 1:50 / ADA 1:48
Cross slope is the one people forget. Turn the level 90 degrees and take it in the same spot.

On site habit: every time you measure a running slope, turn the level sideways and take the cross slope in the same spot. It costs you five seconds and it catches a fault most auditors miss.

4. Measuring a ramp with a digital level

This is the method to use whenever you have the tool.

1

Calibrate

Do this before the first measurement of the day. Then set the level to read in percent.

2

Place it along the slope

Lay the level flat on the ramp surface, pointing straight up the slope. Not at an angle, or you will read a smaller number than reality.

3

Read three points

Take a reading near the bottom, near the middle and near the top. Ramps are rarely poured evenly.

4

Record the steepest

Use the worst reading as the result, not the average. A user has to get up the steepest part, so that is the number that decides whether it works.

Then repeat the whole thing with the level turned sideways for cross slope, and take a reading at the top and bottom landings too, because landings are supposed to be level and frequently are not.

5. If you have no digital level

You can get an accurate answer with a plain 600mm spirit level, a tape measure and a pencil. This is worth knowing because it also explains what the digital level is calculating for you.

1

Rest it on the slope

Put the level on the ramp, pointing up the slope, with the uphill end touching the surface.

2

Lift until level

Raise the downhill end until the bubble is centred. The level is now horizontal.

3

Measure the gap

Measure the vertical gap between the raised end of the level and the ramp surface underneath it.

4

Do the division

Slope equals the gap divided by the length of the level.

A 600mm spirit level held horizontally on a slope, with the gap at the low end markedA spirit level rests on a sloping surface with its uphill end touching the ramp. The downhill end is lifted until the bubble is centred, so the level is horizontal. The vertical gap between the raised end and the ramp surface is then measured. Divide that gap by 600mm to get the slope. A 30mm gap is 1 in 20, a 50mm gap is 1 in 12, and a 12mm gap is 1 in 50 and a 12.5mm gap is 1 in 48. Rest it on the slope, lift the low end until the bubble centres, measure the gap.Measuring slope with a plain spirit levelRest it on the slope, lift the low end until the bubble centres, measure the gap.ramp surfacebubble centred, so the level is horizontal600mm levelmeasure this gapgap 30mm = 1:20gap 50mm = 1:1212mm = 1:50; 12.5mm = 1:48A slope reading alone does not establish a usable ramp.
The whole method in one picture. Gap divided by level length equals the slope.

The numbers for a 600mm level

Because the level is 600mm long, the gap tells you the slope directly.

Gap 30mm ÷ 600mm = 1:20, a 5% running slope.

Gap 50mm ÷ 600mm = 1:12, the upper ordinary ramp slope limit in the profiles below.

Gap 12mm ÷ 600mm = 1:50, the ISO drainage recommendation. A 12.5mm gap is 1:48, the ADA ramp cross-slope maximum.

So with a 600mm level, a gap over 50mm exceeds the ordinary 1:12 slope limit, and a sideways gap over about 12mm means the cross slope is too much. Two numbers to remember and you can audit a ramp with fifteen dollars of tools.

If you work in imperial, the equivalent with a 24 inch level is a gap of 2 inches for 1:12 and half an inch for 1:48. Same idea, different units.

About phone apps

Use them to spot problems, not to write findings

A phone level app is genuinely handy for a quick scan of a site, and a phone is short, so it reads only a small patch of surface and any bump throws it off. Use it to decide where to look properly. Do not put a phone reading in a report as the measured value. If you must use one, rest the phone on a rigid straight edge rather than directly on the ground.

6. Check a named ramp standard

A ramp is a route with landings, usable edges, sufficient space and a dependable surface. First record the applicable standard, edition and project scope. The comparison below uses ISO 21542:2021 ordinary ramps (Table 6) and the 2010 ADA ramp provisions. It does not apply existing-building or kerb-ramp exceptions automatically.

Side view of a ramp showing landings, rise, run, handrails and edge protectionA ramp in side view. A level landing at the bottom, then the sloping run, then a level landing at the top before the door. Handrails run along both sides at a constant height and continue across the landings. A raised kerb runs along the open edge. The rise is the vertical height gained and the run is the horizontal distance travelled. Parts of a ramp to inspect. Check the complete route, not only its slope.doorhandrails both sideskerb along the open edgeriserun (the going)landinglandingParts of a ramp to inspectCheck the complete route, not only its slope.
A ramp is a system. Landings, handrails and edge protection matter as much as the slope itself.
Selected ramp checks: ISO and ADA have different boundaries
CheckISO 21542:20212010 ADA
Running slope and flights6.4.2, Table 6: use the gentlest slope; below 5% preferred. Up to 1:12 where at most 5% cannot be achieved, with gradient-dependent flight limits.405.2 and 405.6: maximum 1:12 and 30in rise per run.
Cross slope6.3.7: drainage cross-fall should be at most 1:50 (2%), subject to exceptional circumstances.405.3: maximum 1:48 (about 2.083%).
Clear width6.4.3: at least 1000mm between rails or obstructions. Surface width also follows traffic requirements in 6.3.3.405.5: at least 36in; between handrails where provided.
Landings6.4.4: end and intermediate landings at least 1500mm long, unobstructed by door swings. Turns and approaches need separate space checks.405.7: at least 60in long and ramp-width wide; direction changes require 60in by 60in.
Handrail trigger6.4.5: at 5% or steeper, both sides when the run exceeds 800mm; at least one side for shorter runs.405.8: runs rising more than 6in require handrails.
Edges and surface6.5: edge protection depends on terrain and drop. 6.4.7: rigid, even surface, slip-resistant wet and dry.405.4, 405.9 and 405.10 cover surface, edge protection and wet conditions.

Read the ISO edition record and ADA section 405. The ISO detail here was checked against the supplied licensed 2021 edition. The full standard and the applicable local requirements still determine the project assessment.

The flight length matters: ISO Table 6 allows 10000mm horizontal run at exactly 1:20, 4500mm at 1:15 and 2260mm at 1:12. Its rounded calculated rises are 500mm, 300mm and 188mm respectively. A blanket 500mm rise rule therefore gives the wrong answer for a steep ISO ramp.

Measure the clear approach as carefully as the ramp. Check door operation, direction changes, resting space, drainage, lighting, rails and the risk of falling from the sides. A slope result describes one measurement; it cannot certify the complete route.

7. Worked examples with a stated reference

Example 1. A 150mm entrance step

The geometry is 150 × 12 = 1800mm of horizontal run at 1:12, or 150 × 20 = 3000mm at 1:20. The sloping surface is slightly longer: √(run² + rise²).

In an ISO Table 6 concept, the 1:12 option sits within the row's flight limits. Adding separate 1500mm end landings gives a straight-line allowance of 4800mm. The 1:20 option needs 6000mm including those landings. Use the lowest feasible slope; these totals do not resolve width or the door approach.

Example 2. A lobby 600mm above the approach

For an ISO Table 6 concept at 1:15, split the rise into two 300mm flights. Each needs 4500mm horizontal run. Include one intermediate and two end landings, each 1500mm: 4500 + 1500 + 4500 + 3000 = 13500mm.

At 1:20, two 300mm flights instead need 6000mm each, or 16500mm including the same landings. These are straight layouts with separate landings; a turning layout needs a plan-space check. At 1:12, the ISO flight limits would require at least four flights. This shows why a steeper slope does not always save as much space as expected. Compare route options, including an appropriate lift, before choosing.

Example 3. Record the worst local reading

A level reads 9.4% near the top, 6.1% in the middle and 5.8% at the bottom. Record all three and identify the worst: 100 ÷ 9.4 ≈ 10.64, or about 1:10.64. Do not replace those readings with their average.

A useful finding is: “The upper entrance-ramp section measures 9.4%, exceeding the 1:12 slope limit in ISO 21542:2021 Table 6. Middle and lower readings are 6.1% and 5.8%.” If an existing-building exception is proposed, document its applicability and complete conditions separately.

8. Use the ramp planner

From a measurement to a layout

The dedicated planner converts rise, horizontal run, ratio, percentage and angle; separates sloping length from plan space; and compares clearly named ISO or ADA profiles. It also includes a measurement mode and a printable result.

Open the ramp planner

For a quick manual check, a 300mm rise over 6000mm horizontal run gives 300 ÷ 6000 × 100 = 5%, or 1:20, and an angle of about 2.86°. The ramp surface is about 6007mm long. End landings are additional plan space; they are not part of the sloping run.

9. Steps and stairs

A ramp is not always the answer. For a big rise a compliant ramp becomes enormous, and plenty of people find a well built stair easier than a long slope, so most places need both. Stairs have their own numbers, and they come off the same tape.

Two measurements describe a step. The riser is the height of one step, and the going is the depth of one tread, front to back. Everything else follows from those two, including the pitch and 2R + G, two risers plus one going. The explorer below uses an illustrative 550–700mm proportion band, a 150–170mm riser range and a 250–450mm going range. These are teaching heuristics, not a combined ISO, ADA or local-code assessment.

Units
mm
mm
Or load an example:

28.8° pitch

2R + G = 630 mm

Enter a riser and a going. This panel needs JavaScript. With it off, the numbers in the paragraph above and the table below do the same job.

A scale drawing of the steps appears here once there is a riser and a going to draw. Every number in it is written out below as well.

A separate ISO reference: ISO 21542:2021 clause 8.3.2 requires uniform, closed risers, a going of at least 260mm and rise no more than 180mm. It recommends 2R + G = 600–660mm. For fire evacuation, a rise no more than 150mm and going at least 300mm are recommended. Clause 8.3.1 recommends no more than 16 risers per flight. The explorer above does not evaluate these requirements, landings, width, handrails or evacuation suitability.

10. Other measurements, with their references

Write the reference next to the number. A door opening, an approach space and a wheelchair turning area serve different movements; one cannot stand in for another. Rounded unit labels are also not interchangeable minimums: 1500mm is less than 60in.

Selected physical access checks, not a complete building specification
ElementReference and selected checkWhat to record
Door openingISO 9.1.1.1: at least 800mm clear, 850mm recommended. ADA 404.2.3: 32in minimum.Actual opening with leaf at 90°, plus manoeuvring space, threshold and opening force.
Path to the buildingISO 6.3.3: 1200, 1500 or 1800mm according to infrequent, frequent or constant two-way traffic.Narrowest usable width; required passing/turning spaces and every obstruction.
Turning and approachingISO 6.6.3: entry approach 1500 × 1500mm; 1500 × 2000mm where a 180° turn is required.Direction of approach, latch-side access, door swing and the actual mobility aids expected.
Clear floor spaceADA 305: 30 × 48in baseline; approach, alcoves and knee/toe space also matter.The free approach to the specific fixture, including permitted overlaps.
Counters and desksISO 10.1 and 9.3.3 distinguish reception counters and seated desk use.Work-surface height, knee/toe recess, reach, hearing support and a usable queue.
ControlsISO 9.2.2: controls 800–1100mm high; at least 600mm from an internal corner. Outlets have a separate exception.Control position, approach, operating force and whether information is visible and tactile.
Accessible toiletISO 10.5.3: layout depends on transfer direction. Side clearance at least 900mm, 1200mm preferred.Clear transfer and manoeuvring spaces, door, rail arrangement, basin and assistance alarm.
StepsISO 8.3.2: uniform rise and going, closed risers; rise at most 180mm, going at least 260mm.Every riser/going, nosing, lighting, contrast and handrail continuity.
WayfindingISO 5.1, 5.3 and 5.5: orientation, multiple senses, visual contrast and signs.Each decision point, sign placement, tactile guidance and consistent destinations.

ISO references in this table mean the 2021 edition. See the physical accessibility guide for the complete journey and source map. All heights are measured from finished floor level, including the installed floor covering.

Plan view of a doorway showing the correct clear width measurementA doorway seen from above with the door opened to 90 degrees. The wrong measurement is shown across the frame from one side to the other. The correct measurement, the clear width, runs from the face of the open door leaf to the stop on the opposite side, and it is noticeably narrower. ISO 21542:2021 requires at least 800mm clear and recommends 850mm. Door clear width, measured correctly. The clear opening is always smaller than the frame.Door clear width, measured correctlyThe clear opening is always smaller than the frame.door leaf, open 90 degreesframe to frame, WRONGclear width, RIGHTOpen the door to 90 degrees.Measure from the face of the doorto the stop on the far side.ISO: 800mm minimum,850mm recommended.
Measuring the frame instead of the clear opening is the most common door mistake on site.
A 60in (1525mm) turning circle and a 30 by 48in clear floor spaceTwo schematic plan shapes illustrate different ADA clearances. A dashed circle 60in (1525mm) across, the ADA circular turning-space option. Beside it a rectangle 760mm wide by 1220mm deep, the clear floor space needed to park in front of a basin, counter or machine. The circle is a little wider than the rectangle is deep. Check permitted knee/toe overlaps and approach.Space to turn and space to parkCheck permitted knee/toe overlaps and approach.60in / 1525mmTURNING CIRCLE180 degree turn760mm1220mmCLEAR FLOOR SPACEat a basin,counter or machine
ADA 304 and 305: schematic circular turning space and clear floor space. Check permitted overlaps, approach and fixture requirements; these shapes are not a universal toilet-room layout.
ISO 21542:2021 control heights A wall elevation marks the 800 to 1100mm zone for control devices under ISO clause 9.2.2. Controls also need at least 600mm clearance from an internal corner; outlets and other devices have separate provisions. Locate controls for a usable approach 1100mm800mm CONTROL DEVICES ISO 9.2.2: check corner clearance, reach and operation as well as height. Finished floor level
ISO 21542:2021 clause 9.2.2. Electrical outlets, meter displays and controls on horizontal surfaces have separate provisions.

11. Running the audit itself

The most common way to produce a bad audit is to wander around measuring interesting things. Follow the journey instead. Walk the building the way a visitor experiences it, in order, and audit each stage as you reach it.

1

Arrival

Parking bays, drop off point, the route from the road or the jetty. Kerbs, crossings and tactile surfaces.

2

Approach

The path to the door. Width, surface, slope, lighting, obstructions and overhanging branches at head height.

3

Entrance

Steps, ramp, door width, opening force, threshold height, and whether the main entrance is the accessible one.

4

Reception

Counter height, knee space, queuing space, hearing loop, and whether signage is readable.

5

Circulation

Corridors, lifts, stairs, handrails, floor surfaces and the clarity of wayfinding.

6

Facilities

Toilets, dining, meeting rooms, guest rooms. Everything the visitor came here to use.

7

Getting out

Emergency exits, refuge points, alarms that flash as well as sound, and an evacuation plan that names who assists whom.

How to record a measurement so it is still useful next month

Every recorded item should carry these seven things. Missing any one of them creates an argument later.

  1. Where. Be specific. "Main entrance ramp, upper third" beats "entrance".
  2. What. The element, such as running slope, clear width, counter height.
  3. The number and the unit. Pick metric or imperial and stay in it for the whole report.
  4. The requirement you compared it to, and which standard that comes from.
  5. Pass or fail, and by how much. "Fails by 15mm" tells someone this is a trim job. "Fails by 400mm" tells them it is a rebuild.
  6. A photograph, ideally with the tape or level in shot showing the reading.
  7. Date and who measured it.

Photograph tip: take two shots of every finding. One close up showing the tape or the level display with the number visible, and one wider shot showing where in the building that close up was taken. Six months later, nobody can identify a close up of an anonymous door threshold without the second photo.

Do the non measurable checks too

Not everything has a number, and the things that do not are often what actually ruins a visit. While you are on site, look for these.

  • Is the accessible toilet being used as a store room? This is extremely common.
  • Is the accessible parking bay the furthest from the door, or blocked by cones?
  • Does the ramp lead to a door that is kept locked?
  • Do staff know where the portable ramp is, and can they find the key for the lift?
  • Is the hearing loop switched on and does anyone know how to test it?
  • Is the accessible route signposted from the point where you have to choose?

12. Mistakes to avoid

  • Measuring once. Surfaces vary. Three readings minimum, always report the worst.
  • Forgetting cross slope. Turn the level sideways every time.
  • Measuring the door frame. The clear opening is smaller than the frame, because the door leaf sits in the way. Always open it to 90 degrees first.
  • Averaging readings. Users have to negotiate the worst point, not the average point.
  • Mixing units mid report. Decide at the start and stay consistent.
  • Trusting an uncalibrated level. Calibrate daily.
  • Only checking the way in. Getting out in an emergency is part of the audit.
  • Writing "not compliant" with no number. Always record the actual measurement, the target, and the gap between them.

13. A record sheet to take with you

Everything above only helps if it gets written down at the time. Memory is not a measuring tool. Print this, put it on a clipboard, and fill in a copy for every ramp and every entrance you look at. One sheet per element, so nothing gets merged by accident.

Two habits make the sheet worth having. Always write the number you actually measured, even when it passes, because the next person needs a baseline. And when a measurement is outside the selected requirement, write the number and the relevant clause. A redesign needs the whole layout: simply adding ramp length may introduce new landing, turning or door-clearance problems.

Site

Element and location

Date

Auditor

Standard, edition, scope and clause

Weather and surface condition

Field record sheet. For each check, the target and how to take the reading, then blank columns to write the measured value, whether it passed, and a note.
Check Target, and how to take it Measured Result Note or gap
Running slope Selected slope and flight rule: ______ISO Table 6 / ADA 405; record all local readings
Cross slope ISO: 1:50 recommendation / ADA: 1:48 maxSelect reference; level sideways
Clear width ISO: 1000mm between rails / ADA: 36inAlso check required surface width
Rise per flight ISO: gradient-dependent Table 6 / ADA: 30inRecord each flight rise and horizontal run
Landing, bottom ISO: 1500mm length / ADA: 60in lengthAlso width, slopes and obstructions
Landing, top ISO: 1500mm length / ADA: 60in lengthAlso turn, door approach and swing
Handrails Apply ISO 6.4.5 + 8.4 / ADA 405.8 + 505Trigger, sides, height, grip and extensions
Edge protection Apply ISO 6.5 / ADA 405.9Record adjacent terrain, drop and protection
Surface Firm, stable, slip resistant wetNote the material
Approach, top and bottom Clear, no narrow inward doorNote obstructions
Door clear width ISO: 800mm / ADA: 32in baselineFace of leaf to stop, open 90°
Door opening force Light enough to push one handedNote if a closer fights you
Turning space Selected manoeuvring requirement: ______Record turn angle, width and depth
Controls and handles ISO 9.2.2: controls 800–1100mm; device exceptionsSelect device type, reach and approach

Photographs taken, and anything the table has no room for

The last box matters more than it looks. Photograph every failure with something in shot for scale, a tape or the level itself, and note the file number on the sheet. A photograph with a tape measure in it ends arguments that a paragraph never will.

That is the built environment covered. Part 4 does the same job for a screen: testing what you build, with a fifteen minute pass, real screen reader keystrokes and a record sheet of its own. Or go back to part 1 on the core concepts or part 2 on the standards, and use the resources page for the tools and references mentioned throughout.